Home Embedded Vulns General Vulns

CVE-2019-19279

HIGH 7.5

Our Analysis: Environment Specific

Our model has classified this vulnerability as relevant to Environment Specific Systems, helping your team prioritize efforts effectively.

Published Date March 10, 2020
Last Modified November 21, 2024
CVSS Vector Not Available

Description

A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.

Potentially Affected Vendors