Home Embedded Vulns General Vulns

CVE-2019-5170

HIGH 7.8

Our Analysis: Environment Specific

Our model has classified this vulnerability as relevant to Environment Specific Systems, helping your team prioritize efforts effectively.

Published Date March 12, 2020
Last Modified November 21, 2024
CVSS Vector Not Available

Description

An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). A specially crafted XML cache file written to a specific location on the device can be used to inject OS commands. An attacker can send a specially crafted packet to trigger the parsing of this cache file.At 0x1e87c the extracted hostname value from the xml file is used as an argument to /etc/config-tools/change_hostname hostname=<contents of hostname node> using sprintf(). This command is later executed via a call to system().

Potentially Affected Vendors